XM31-915-HP
Batteries
 
 

Alarms
 

Battery
 

Batteries
Battery String Voltage 40.47 V
Runtime Remaining Over three hours
Battery Life Remaining Over five years
Battery Balancing Disabled
Balancing String Not balancing
Battery Temperature 10 °C
50 °F
  1 2 3 Balancing
String A 13.50 V 13.52 V 13.54 V Normal
Battery Charging
Charger Mode Rest
Current Charger Mode Time 573 min
Charger Current 0.00 A
Charger Current Limit 10.50 A
Charger Enable Yes
Configuration
Technician ID 0
24 Hour Battery Refresh No
Battery Model 4.0HP
Accept Voltage 2.35 V/cell
Float Voltage 2.25 V/cell
Refresh Voltage 2.45 V/cell
Battery Capacity 114 Ah
Temperature Compensation 4.00 mV/cell/°C
HP Battery Rest Mode Yes
Battery String Detect Auto
Number of Battery Strings 1
Heater Mat Installed No
Conductance
Last Conductance Measurement 2000-01-01
  Last Adjusted Conductance Measurement Manufactured Date
String A Battery 1 0 S(℧)  
String A Battery 2 0 S(℧)  
String A Battery 3 0 S(℧)  

 
Copyright © 2017-2022 EnerSys. All Rights Reserved.
www.alpha.com   |   www.enersys.com